Scinovex
articleTop 1% cited

Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC Converter

IEEE Transactions on Power Delivery · 2014 · Vol. 29(5) · pp. 2287–2296
Jenny Zheng ZhouHui DingShengtao FanYi ZhangA.M. Gole

Abstract

The impact of phase-locked loop (PLL) parameters on the dynamic and steady-state behavior of a voltage-source converter (VSC) in an HVDC transmission system is determined as a function of the system strength [parameterized by the short-circuit ratio (SCR)]. This is achieved by using a linearized small-signal model of the converter system and its controls. The model is validated via electromagnetic transients simulation of the fully detailed large signal model. An interesting result from this study is that the maximum power transfer capability of the VSC-HVDC converter is affected by the PLL gains, and that the theoretical limit (obtained from static voltage stability analysis) is approachable as the PLL gains become very small. This paper shows that gains of the PLL, particularly at low SCRs, greatly affect the operation of the VSC-HVDC converter and that operation at low SCRs approaching 1.3 is very difficult.

Microgrid Control and OptimizationHVDC Systems and Fault ProtectionHigh-Voltage Power Transmission SystemsPhase-locked loopHVDC converterControl theory (sociology)Voltage sourceMaximum power transfer theoremEngineeringTransfer functionShort circuit ratioSIGNAL (programming language)Small-signal model

Funding

  • Manitoba Hydro
Citations
732
FWCI
28.31
field-weighted impact
References
22
Percentile
100%
vs. same field & year
Citations per year
Cited by
Definition and Classification of Power System Stability – Revisited & Extended
IEEE Transactions on Power Systems · 2020 · 1,028 citations
References
Citation Network

How this paper connects to the literature. Drag to explore, click any node to open that paper.