Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC Breakers

IEEE Transactions on Power Delivery · 2014 · Vol. 31(3) · pp. 973–981
Jeremy SneathAthula Rajapakse

Abstract

Different HVDC grid types and the respective protection options are discussed. An earthed bipole HVDC grid was modeled in PSCAD, and using simulation results, the necessity of di/dt limiting inductors to contain the rise of fault currents within the capacity of current hybrid dc breakers is demonstrated. The impact of different inductor sizes on current rise was studied. A fault detection and localization scheme using the rate of change of voltage measured at the line side of the di/dt limiting reactors is proposed. The protection system was modeled and tested under different fault types and locations. The results show that the proposed method of HVDC grid protection is feasible using the current hybrid dc breaker technology. A systematic procedure for setting the necessary protection threshold values is also demonstrated.

HVDC Systems and Fault ProtectionHigh-Voltage Power Transmission SystemsElectrical Fault Detection and ProtectionCircuit breakerInductorFault current limiterGridFault (geology)Transient recovery voltageEngineeringCurrent limitingElectrical engineeringLimiting
Citations
455
FWCI
12.55
field-weighted impact
References
17
Percentile
99%
vs. same field & year
Citations per year
References
Locating and Isolating DC Faults in Multi-Terminal DC Systems
IEEE Transactions on Power Delivery · 2007 · 635 citations
Citation Network

How this paper connects to the literature. Drag to explore, click any node to open that paper.

Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC Breakers · Scinovex