Scinovex
articleTop 10% cited

Modeling of DFIG-Based Wind Farms for SSR Analysis

IEEE Transactions on Power Delivery · 2010 · Vol. 25(4) · pp. 2073–2082
Lingling FanRajesh KavasseriZhixin MiaoChanxia Zhu

Abstract

This paper conducts an analysis of subsynchronous resonance (SSR) phenomena in doubly-fed induction generator (DFIG)-based wind farms interconnected with series compensated networks. A dynamic model is developed to analyze the induction generator effect (IGE) and torsional interaction (TI) in such systems. A test system derived from the IEEE first benchmark model is considered for the analysis. The effect of two factors namely: 1) series compensation level and 2) wind speed on the IGE and TI are studied. In addition, impact of the inner current converter controller parameters and turbine parameters on SSR is also addressed. Small signal (eigenvalue) analysis is conducted to assess the damping of network and torsional modes followed by dynamic (time domain) simulations. The major contribution of this paper is the analytical investigation on SSR phenomena presented in DFIG-based wind farms interconnected with series compensated networks. The paper clearly demonstrates that IGE instead of TI is the major reason for SSR in such systems.

Wind Turbine Control SystemsMicrogrid Control and OptimizationHVDC Systems and Fault ProtectionControl theory (sociology)Doubly fed electric machineInduction generatorTurbineController (irrigation)Wind powerEngineeringBenchmark (surveying)Eigenvalues and eigenvectorsCompensation (psychology)
Citations
469
FWCI
12.62
field-weighted impact
References
24
Percentile
99%
vs. same field & year
Citations per year
Cited by
Definition and Classification of Power System Stability – Revisited & Extended
IEEE Transactions on Power Systems · 2020 · 1,028 citations
Citation Network

How this paper connects to the literature. Drag to explore, click any node to open that paper.